Call us 24/7 usadcs@163.com

GE 8044-CC-20 Carrier extension cable, 2.0m

GE 8044-CC-20 Carrier extension cable, 2.0m

On-line download

Users with safety responsibility can
download new parameters to a SafetyNet
Controller, from a Trusted Host, to a
Controller whose Key Switch is set to permit
new downloads and where the particular
SafetyNet Controller’s Password is known.
New parameter download is carried out as a
background task over a number of cycles to
ensure that the fault reaction and response
times are not compromised. Once download
is complete and the new parameters have
passed the checking and security tests, the
new parameters will be automatically
adopted. Where redundant SafetyNet
Controllers are used, the stand-by Controller
will also be automatically updated.
Note: on-line download should only be used
where there are adequate procedures for
approving the changes that have been made
and testing them prior to download.
Static Analysis Tool
Any safety-related application program must
be developed by suitably qualified personnel
and must be subject to careful scrutiny to
ensure safety, but the Workbench provides
an additional safety test. The Static Analysis
Tool checks for illegal constructs within the
safety program prior to download.
Differences Utility
Once a new SafetyNet application is
successfully compiled, it can be downloaded
to a SafetyNet Controller. On download, two
text reports are generated: a Download
Report and a Master Tag Xref. These can be
used for comparison with other downloads
using the Differences Utility.
Download backup
A time stamped backup of each safety
application is automatically created
following a successful download. Changes
between versions can be viewed and
backups can be used either as a start point
for developing new safety applications or to
restore an earlier version.
Change Control Log
The Workbench maintains a Change Control
Log that records – for example – when:
♦ IO Modules are added, deleted or moved
♦ Tags are added to, removed from, or
moved within an IO Module
♦ IO Configuration parameters are saved
♦ Controller IP addresses or node
numbers are entered or modified
♦ External node numbers are entered or
modified
♦ Serial communications parameters are
entered or modified
♦ A successful download is made
♦ A Strategy is removed
♦ The Controller password is changed

General
SafetyNet IO Modules interface to safety
system field wiring via Field Terminals.
The IO Modules and the Field Terminals
mount on Carriers that provide
mechanical support, but also connect the
internal communication bus and power
supply connections to the Modules.
The IO Modules are certified as suitable
for use in SIL 2 safety-related
applications.
Certification
The SafetyNet IO Modules are certified for
use in safety-related applications up to and
including SIL 2. The SafetyNet System
achieves this certification with a 1oo1D
architecture.
The SafetyNet IO Modules have been
designed specifically for safety-related
applications and are certified on the basis of
the excellence of their design. The
certification does not depend on “proven in
use” data.
Diagnostics
The IO Modules perform comprehensive
internal diagnostic tests as an essential part
of ensuring that the IO can carry out the
required safety function.
If the SafetyNet IO Module’s internal
diagnostics detect a fault that would prevent
the SafetyNet System from carrying out its
safety function, then it will initiate a controlled
shutdown. A controlled shutdown has two
objectives – firstly, to ensure that the IO
Module enters its failsafe mode; and
secondly, to record sufficient data to allow the
reason for the shutdown to be determined.
If a SafetyNet Module enters a controlled
shutdown, then all IO channels are de activated: input channels are not scanned;
and output channels are de-energised.
Bussed Field Power
The Bussed Field Power (BFP) connectors on
the rear of IO Module Carriers provide the
power connections for field instruments
wired to the IO Modules.
For the SafetyNet System, BFP must be 24V
dc and supplied by MTL’s 8914-PS-AC units.
These power supplies may be used in
redundant pairs, if required.
Live maintenance
SafetyNet IO Modules can be removed and
replaced in a Class 1, Division 2 or Zone 2
hazardous area – once the relevant Bussed
Field Power (BFP) connection has been
isolated using an appropriate hazardous
area switch (such as the MTL951). Removing
and replacing the Modules does not
interrupt the operation of the other parts of
the node.
If a Module is replaced by another Module
of identically the same type, then no
intervention is required for the System to
begin operating normally once the Bussed
Field Power is restored.

GE 8021-CE-LH Carrier extender, left hand

GE 8021-CE-LH Carrier extender, left hand

Line fault monitoring
In addition to the comprehensive internal
diagnostics the SafetyNet IO Modules can
monitor field wiring for line faults.
Event logging
Data from SafetyNet IO Modules can be
time stamped and stored by the SafetyNet
Controller before being downloaded to the
MOST SOE Data Retrieval Client or a 3rd
party historian package. SafetyNet IO
Module data is time stamped with a
resolution of better than 200ms.
Failsafe Mode
IO Modules will enter Failsafe Mode from
the Running State either due to loss of
communications with the Controller or
because the module has received an
instruction from the Controller to enter the
Failsafe State. In this state:
♦ The Red Fault LED is lit
♦ The IO Module is flagged as unhealthy
to the Controller
♦ All Railbus Write requests are rejected,
except instructions to Reset or to exit the
Failsafe State
♦ Inputs and HART data are read
♦ Outputs are de-energised
♦ Background diagnostics continue and if
a failure is detected, the module will
enter Controlled Shutdown
Controlled Shutdown
A Controlled Shutdown is carried out if a fault
is detected in the Module. In this state it can
communicate the reason for shutdown.
LED’s
A number of LED’s are provided on each IO
Module to provide visual indication of the status
of the Module, its channels and its power supply.
Module ‘Fault’ LED (red)
On – Failsafe
Off – Normal operation
Flashing (equal:mark space ratio) – Cold
start in process, will flash until
communication is established with SafetyNet
Controller.
Blinking (On for a short period, then On
for a longer period – morse code ‘a’) – Fault
state after controlled shutdown
Module ‘Power’ LED (green)
On – Power OK
Off – BFP or Railbus Power Failure
Module ‘Channel’ LED’s
(yellow)
See Individual Module Specifications

Diagnostics
The SafetyNet Analogue Input Module carries
out a number of diagnostic checks to confirm
the accuracy of the measurement reported
and the correct operation of the module.
In addition to the primary measurement, a
second diagnostic measurement is made
using different internal circuitry. The two
values are then compared. The primary
measurement is reported as faulty if it differs
from the diagnostic measurement value by
more than 2%.
Further tests are carried out on internal
supply and references voltages.
If a particular channel fails a test, then that
channel is made inactive. If the failed test
indicates that the Module is not working
correctly, it will enter Controlled Shutdown.
Live maintenance
The field wiring connections to the SafetyNet
Analogue Input Module are classified as
non-incendive and can therefore be live
worked in a Class 1, Division 2 or Zone 2
hazardous area.
(Note the Bussed Field Power connection
must be isolated before the module is
removed or replaced).
Input sampling and filtering
Each input channel is sampled once every
25ms and is filtered by 1st order hardware
and software filters. The software filter can
be disabled or set to a number of different
values according to the filtering

requirements of each channel.

General
The SafetyNet Analog Input Module with
HART provides the interface to 8
channels of 4-20 mA input signals.
The SafetyNet Analogue Input Module is
certified for use in safety-related
applications up to SIL 2. In such
applications the module is used with the
8851-LC-MT SafetyNet Controller and
8811-IO-DC SafetyNet Discrete
Input/Output Module.

GE 8080-FC-10 16-pin cable for 8618 (1m)

GE 8080-FC-10 16-pin cable for 8618 (1m)

HART capability

The HART capabilities of the Analogue Input
Module allow acquisition of secondary
variables – which can be used by a standard
(but not SafetyNet) application program.
The Module also allows Emerson’s AMS
package to communicate with any HART
field device transparently, using HART passthrough. (The first release of SafetyNet will
not have full HART capability, contact MTL
for further information).
LED’s
For the operation of the Power and
Fault LED’s see IO Module Overview.
Module ‘Channel’ LED’s
(yellow)
On – Channel in range (4-20mA)
Off – Channel inactive
Flashing (equal:mark space ratio) – Any of
the following, with an active channel: line
fault (indicated by the input measurement
being outside the 4-20mA range), loss of
HART signal, Hi-Hi or Lo-Lo alarm.
Alarms, Deadband, Dead Zone
The Analogue Input Module has a number
of configurable parameters for managing
setting and clearing alarms and triggering
the reporting of a new input value.
Hi, Hi-Hi, Lo and Lo-Lo alarms can be
configured – together with a Deadband
through which the input must move before
the alarm is cleared. The relationship
between these parameters is shown in the
diagram below.
A Dead Zone can also be configured, which
is the value by which an input measurement
must change before it is reported as a new

value.

♦ 8 single ended 4-20mA input channels

♦ Certified for use in SIL 2 safety applications
♦ Non-incendive field circuits
♦ 2-, 3- or 4-wire transmitters
♦ HART pass-through, acquisition and status reporting*
♦ 24V dc Bussed Field Power required from 8914-PS-AC
MODULE SPECIFICATION
See also System Specification
INPUTS
Number of channels ………………………………….8, single-ended
Nominal signal range (span) ………………………………4 to 20mA
Full signal range …………………………………………..0.25 to 24mA
Line fault detection
Short circuit current ………………………………………………..> 23.5mA
Open circuit current ………………………………………………..< 0.5mA
Output voltage (@ 20mA)………………………………….10.2V (min.)
Output current ………………………………………………28mA (max.)
Accuracy (at 25oC) ……………………………………….± 0.1% of span
Temperature coefficient ……………………………………..38 ppm/C
Resolution ………………………………………………………………16 bits
Repeatability ………………………………………………0.05% of span
Data format ………………..16-bit unsigned (0-25mA = 0-65,535)
HART data format ………………………………IEEE754 floating point
Isolation
(any channel to Railbus) ……………………………………..250V ac RMS
(between channels) ……………………………………………………….none
CONFIGURABLE PARAMETERS
Alarms. ………………………………..high, high-high, low and low-low
Alarm deadband (hysteresis) ……………………..user defined value
Input filter time constant …………………………user defined value
Input dead zone ……………………………………..user defined value
Drive on fault state ………………….disabled /upscale /downscale
HART variable and status reporting ………….. enable /disable
RESPONSE TIME
Signal change to availability on Railbus
4– 20 mA mode ………………………………………………..25ms (max.)
HART mode………………………………………………..0.75s per channel
* The first release of SafetyNet will not have full HART capability,
contact MTL for further information.

GE 8030-CE-RH Intrinsically Safe Carrier extender, right hand

GE 8030-CE-RH Intrinsically Safe Carrier extender, right hand

HAZARDOUS AREA SPECIFICATION
Protection Technique……………………………….EEx nA [nL] IIC T4
Location (FM and CSA) …………Class 1, Div.2, Grps A,B,C,D T4
(CSA with non-incendive field terminal, subject to conditions in CSA
certificate.)
FM non-incendive field wiring parameters (each channel)
……………………………………………………..Voc = 28.7V; Isc = 33mA
Gas groups A, B …………………………….Ca = 0.17µF; La = 11mH
Gas group C ………………………………….Ca = 0.51µF; La = 33mH
Gas group D ………………………………….Ca = 1.36µF; La = 88mH
POWER SUPPLIES
System Power Supply………………….50mA (typical), 70mA (max.)
Bussed Field Power Supply
……………………..350mA (2-wire TX max.), 110mA (4-wire TX max.)
MECHANICAL
Module Key Code …………………………………………………………A1
MODULE WIDTH ……………………………………………………..42mm
WEIGHT ……………………………………………………………………200g
For recommended and compatible Field Terminals, see
Field Terminal – Specification and Selection Guide.
General
The SafetyNet Discrete Input/Output
Module provides the interface to 8
channels that may be configured in any
combination of discrete inputs and
outputs.
The SafetyNet Discrete Input/Output
Module is certified for use in safety related applications up to SIL 2. In such
applications the module is used with the
8851-LC-MT SafetyNet Controller and
8810-HI-TX SafetyNet Analogue Input
Module with HART.

Combined inputs and
outputs
Each of the 8 channels of the SafetyNet
Discrete Input/Output Module may be
configured, on a channel-by-channel basis,
as either an input or an output.
When configured as an input, the channel is
suitable for use with dry contacts – with
power supplied from the Module.
When configured as an output, the channel
is capable of switching up to 2.0A
(maximum of 6.0A continuous per module).
Output channels are used with solenoids,
valves and alarms
Diagnostics
Comprehensive diagnostic tests are
performed on the module and each of its
channels, including tests for stuck ON and
stuck OFF output switches.
Live maintenance
The field wiring connections to the SafetyNet
Discrete I/O Module are classified as non sparking and can only be worked on in a
Class 1, Division 2 or Zone 2 hazardous
area once the Bussed Field Power
connection has been isolated.
Note: the Bussed Field Power connection
must also be isolated before removing or
replacing the module.
Input configuration
Input channels are used to interface to volt
free contacts. Line fault detection can be
turned OFF or can detect open circuits or
both open and short.
Input filtering
A change in the input state is recorded only
if the states observed at the start and end of
the filter time interval are the same. If they
are different the previous state is
maintained. (This reduces the chance of
noise being incorrectly interpreted as a
change of input value).
The filter time interval can be configured
between 0 and 8s, in 1ms intervals.
Input transition counting
A counter can record the number of filtered
transitions of a particular type. Depending
on the polarity setting, the counter will either
count transitions from 0 to 1, or from 1 to 0.
The counter “wraps around” from 65 535 to
zero without indication.
Transitions are counted even if the channel is
configured to “latching”.
Earth leakage detection
Where earth leakage fault detection is
required, a single channel of an 8811-IO DC module must be configured to monitor
earth leakage and wired to the appropriate
terminals of an 8751-CA-NS Controller
Carrier.
Input latching
Inputs can be configured to “latch” a
particular (filtered) input transition and
maintain the output in the latched state until
the latch is cleared. “Normal Polarity” will
latch a transition from 0 to 1 as 1, “Inverse
Polarity” will latch a transition 1 to 0 as 0.
The operation is described in figure 1.

GE 8034-CC-12 Intrinsically Safe Carrier Extension

GE 8034-CC-12 Intrinsically Safe Carrier Extension

♦ 8 inputs – any combination of inputs and outputs
♦ Certified for use in SIL 2 safety applications
♦ Non-arcing inputs and outputs
♦ Output channels rated up to 2A continuous
♦ Inputs for dry contact switches
♦ 24Vdc Bussed Field Power required from 8914-PS-AC
MODULE SPECIFICATION
See also System Specification
Number of channels ……………………………………………………..8
(independently configured as inputs or outputs)
INPUTS
ON/OFF threshold current ………………………………0.9mA (typ.)
O/C Voltage………………….24V dc (typ.) – depends on BFP Supply
Wetting current ………………………………………………1.2mA (typ.)
Minimum pulse width detected………………………………….5ms
Max input frequency in pulse counting mode (no debounce) 30Hz
Isolation (any channel to Railbus)…………………………………250V ac
OUTPUTS
Maximum Output Current per Channel …………………………..2A
Maximum Output Current per Module
Continuous …………………………………………………………………………….6A
Non-continuous (<10 seconds)………………………………………………….8A
INPUT CONFIGURABLE PARAMETERS
Filter time interval ………………………………0 to 8s (in 1ms steps)
Earth Leakage Detection Channel ……………………….ON/OFF
Latch inputs ………………………………………………..enable /disable
Latch polarity ………………………………latch on high/latch on low
Pulse counting ………………..up transition/down transition/disable
Line fault detection………. none/open circuit/open & short circuit
OUTPUT CONFIGURABLE PARAMETERS
Output type ……………………………………….pulse/discrete/pattern
Pulse width……………………………………………………….1ms to 60s
Line fault detection*……….open line & short circuit detect /disable
* Normally de-energised channels only
RESISTANCE MEASUREMENT ACCURACY
For normally de-energised output open and short-circuit
detection.
With forward biased test current
……………………………… ±(3.4%+5.3Ω) for line resistance ≤ 220Ω
..greater of: ±7% or ±(3.1%+27Ω) for line resistance >220Ω, <1kΩ
With reverse biased test current
…………………………………………greater of: ±7% or ±(3.1%+430Ω)
RESPONSE TIME
Input Signal change to availability on Railbus …..5ms (max.)
Railbus command to output change …………………..1ms (max.)

HAZARDOUS AREA SPECIFICATION
Protection Technique…………………………………EEx nA nL IIC T4
Location (FM and CSA) …………Class 1, Div.2, Grps A,B,C,D T4
POWER SUPPLIES
System Power Supply ……………………50mA (typ.), 70mA (max.)
Bussed Field Power Supply
All channels configured as inputs …………………………..50mA (max)
Any channels configured as output……50mA + output load currents
MECHANICAL
Module key code …………………………………………………………B6
Module width …………………………………………………………42mm
Weight ……………………………………………………………………..210g
For recommended and compatible Field Terminals, see
Field Terminal – Specification and Selection Guide.

GE 8085-FC-10 20 + 24 pin cables for 8619 (1m)

GE 8085-FC-10 20 + 24 pin cables for 8619 (1m)

Power and communication

Carriers distribute “system” power to IO
Modules and provide the communications
route between Controllers and IO Modules.
(Controller power is supplied by direct
connections to the Controllers themselves).
IO Module Carriers provide connectors
through which field power can be supplied
(see “Bussed Field Power”). Note: field
power to Intrinsically Safe IO is managed
differently, see the relevant 2/1 data sheets.
Multi-pin connectors at the end of each
carrier allow further Carriers to be added–
and the “system” power supply and
“Railbus” connections to be made.
Earthing screens and shields
All I/O Module Carriers have their own
independent earthing/grounding strip
to terminate the screens/shields of field
wiring cables.
SafetyNet Controller Carrier
The SafetyNet Controller Carrier (8751-CA NS) is the dedicated Carrier for the
SafetyNet System. It can support simplex or
redundant SafetyNet Controllers and the
Power Supply Monitor (8410-NS-PS).
Serial communications
Two D-type connectors are provided on the
SafetyNet Controller Carrier for connecting
to serial devices. These link to Serial Port “1”
of Controller A and Controller B.
A second pair of D-type connectors is found
on the Controllers themselves, to provide
connections to Serial Port “2” where
redundant serial communication is required.
Further details of the serial port connections
are given in the data sheet for the SafetyNet
Controllers and Carriers.
Controller Carriers
Two Controller Carriers are available – the
standard Controller Carrier and the ELFD
Controller Carrier.
To comply with the earth leakage fault
detection (ELFD) requirements of Fire & Gas
application standards, the ELFD Controller
Carrier (8751-CA-NS) can be used. A single
channel of an 8811-IO-DC module must be
allocated to earth leakage detection to
implement this function.
SafetyNet applications that do not require
ELFD can use the standard Controller

Carrier (8750-CA-NS)

Change State buttons

Two change state buttons are mounted on
the SafetyNet Controller Carrier – one for
each Controller. The button is used to switch
a master to being the standby in a
redundant pair, to switch a standby offline
and to instruct an offline standby Controller
to synchronise itself with the Controller and
to enter standby.
Terminations for power fail
inputs
The 8913-PS-AC and 8914-PS-AC power
supplies each have an output that indicates
the health of the supply. These outputs can
be connected to the termination block on the
SafetyNet Controller Carrier and are used
by the Power Supply Monitor Module to
detect failures in any of up to 7 of these
external power supplies.
Module Carrier
SafetyNet Systems use the 8-module Carrier
with 64-slot addressing (8709-CA-08) for
SafetyNet and standard modules.
Up to 8 of these may be used together to
provide slots for up to 64 IO Modules.
The 4-module Carrier (8710-CA-04) can be
used where the application requires four IO
Modules or less. This will modify the
addressing system and users should should
contact MTL when considering this option.
Carrier Extenders and Cables
To allow for flexibility in cabinet layout,
Carrier Extenders are provided which –
together with the Extender Cables – are used
to connect Carriers mounted on different
sections of the cabinet backplane or DIN
rail. Carrier Extenders are used in left- and
right-hand pairs

GE 8041-CC-35 Carrier extension cable, 0.35m

GE 8041-CC-35 Carrier extension cable, 0.35m

The ELFD Controller Carrier provides a mounting platform for up to
two SafetyNet Controllers (8851-LC-MT). It can also accommodate a
Power Supply Monitor module (8410-NS-PS) which can monitor the
health of up to two 8913-PS-AC, four 8914-PS-AC power supplies
and the 12V supply to Intrinsically Safe Modules (when these are
used). For each Controller there is a serial port connector and a
manually operated ““Change State” button. The Carrier also
provides terminals that are used when earth leakage fault detection
is required.
CARRIER SPECIFICATION
See also System Specification
CARRIER MOUNTING MODULES
SafetyNet Controller (x2) ………………………………..8851-LC-MT
Power Supply Monitor Module …………………………8410-NS-PS
ELECTRICAL CONNECTIONS
Railbus connector ………………………………………………..male out
Serial port connectors……………………9-pin, D-type (female) (x2)
Power Fail connections ……………………screw terminals (x7 pairs)
Ground connection …………………………….M4 screw terminal (x1)
BFP0V connection ………………………………M4 screw terminal (x1)
Earth leakage fault detection connections
…………………………………………………………screw terminals (1 pair)
System Power connections………………………………..6-Pin (male)
(Note: this does not provide power to the SafetyNet Controllers)
MECHANICAL
Dimensions …………………………..200 (w) x 253 (d) mm (footprint)
Height ……………………………………….28 mm (top of circuit board)
…………………………………………………………………..55 mm (overall)
Weight ……………………………………………………..1.43 kg (approx.)
Mounting methods ………………………………..flat panel (4 fixings)
USER CONTROLS
Two “ change state” buttons, one for each SafetyNet Controller, are
provided on the carrier. The state change depends upon the
controller state before the button is pressed. See table below for
effects.
Controller Carrier
ELFD Controller Carrier 8751-CA-NS
State Effect
Master Change to standby if current standby is healthy
Standby Change to offline state
Backup Re-synchronise and return to standby

EARTH LEAKAGE FAULT DETECTION
SYSTEM POWER SUPPLY CONNECTIONS
Pin # Function
1 0V
2 NC
3 Tx/Rx (+)
4 Tx/Rx (+)
5 Tx/Rx (-)
6 Tx/Rx (-)
7 NC
8 NC
9 0V
Terminal External Power
1 No connection
2 0V
3 +12V
4 +12V
5 0V
6 No connection
Two pairs of System Power supply connections (terminals 2/3 and
terminals 4/5) are provided for wiring a redundant pair of 8913-PSAC power supplies.
Note: The Controllers do not draw their power from these
connections, they are supplied with Controller Power via connections
on the Controllers themselves.
The GND terminal must always be connected to the main instrument
earth or the ‘star-point’ bus-bar. (Note: the 0V of the 8913-PS-AC
power supplies is GND).
The BFP0V terminal must always be connected to 0V of the 8914-PSAC power supplies.
Controller Carrier
When earth leakage fault detection is NOT required, a link should be
made – as shown below – between the BFP0V and GND connection
studs. Note: the BFP0V connection stud must still be connected to
Bussed Field Power 0V, marked “-” on the 8914-PS-AC power supply,
and the GND connection must still be connected to ground.
When earth leakage fault detection IS required, then the terminals of
connector CON12 must be wired to a channel of an 8810-IO-DC
module – as shown below – that has been configured for earth
leakage. Note: earth leakage fault detection can only operate when
BFP0V and all field wiring and field instruments are isolated from
ground (GND).

GE 8086-FC-20 20 + 24 pin cables for 8619 (2m)

GE 8086-FC-20 20 + 24 pin cables for 8619 (2m)

An 8410-NS-PS Node Services Power Supply Monitor Module must be

installed on the Controller Carrier to make use of this capability. If an8410-NS-PS is not being used, then it is not necessary to make anyconnections to the PSU Power Fail terminalsTerminal pairs 1, 2, 4 and 5These terminal pairs are used to monitor the AUX (or power fail)output from up to four 8914-PS-AC power supplies.The upper terminal of each pair is connected directly to the AUXterminal of the 8914-PS-AC that is to be monitored. It is notnecessary to connect the lower terminal – as this is internallyconnected to the BFP0V terminal on the Carrier.If any of the 8914-PS-AC supplies are acting as redundant pairs,then these should be connected to terminal pairs 1 and 2 and/ orterminal pairs 4 and 5.If a pair is unused, a shorting link must be placed between the upperand lower terminals, otherwise the Power Supply Monitor Module willcontinuously report a fault.Terminal pair 3The upper terminal of this pair should be connected to the 24V dcsupply of the 8914-PS-AC supply monitored by terminal pairs 1 and2. The lower should be connected to the 24Vdc supply of the 8914-PS-AC monitored by terminal pairs 4 and 5.If a single pair of 8914-PS-AC power supplies is being monitored,then it is only necessary to make single connection to appropriateterminal of pair 3.Terminal pair 6

This terminal pair is unconnected and should not be used.

Terminal pairs 7 and 8

These terminal pairs are used to monitor the AUX (or power fail)output from up to two 8913-PS-AC power supplies.The upper terminal of each pair is connected directly to the AUXterminal of the 8913-PS-AC that is to be monitored. It is not necessaryto connect the lower terminal – as this is internally connected to theGND terminal on the Carrier.If a pair is unused, a shorting link must be placed between the upperand lower terminals, otherwise the Power Supply Monitor Module willcontinuously report a fault.Terminal pair 9If a Railbus Isolator (8922-RB-IS) is not used in the node, this terminalpair must be fitted with a shorting link to prevent an alarm conditionbeing signalled to the Controller.If a Railbus Isolator is used, internal connections are made to monitorthe failure of any power supplies used to provide power for theIntrinsically Safe IO Modules.ELECTRICAL CONNECTIONSRailbus connectors ……………………………….female in, male outCable screens/shield connections…M4 screw terminals (x34)Bussed field power supply connectors………8-pin male (x2)The two 8-pin connectors provided at the top rear of the carrierconnect power supplies for ‘field power’. These supplies are routedthrough I/O modules that require power for their field circuits.MECHANICALDimensions ……………………………342 (w) x 170 (d) x 22 (h)mmWeight ……………………………………………………………………680gMounting methods…………………………….Flat panel or DIN railDIN-rail types……….‘Top hat’ 35 x 7.5mm rail or 35 x 15mm rail to EN 50022………………………………………………..G-section rail to EN 50035Note: For applications with up to 4 IO Modules, it is possible touse the 4-module Carrier (8710-CA-04). For further information,contact MTL.

GE 8042-CC-85 Carrier extension cable, 0.85m

GE 8042-CC-85 Carrier extension cable, 0.85m

◆ ensures Railbus and power supply continuity
◆ pairs (left & right hand) link separate carrier runs
◆ sub-D connectors linked via multi-way cable
◆ multi-pin connector to carrier
◆ maximum of 3 extender pairs per node
◆ 32- and 64-slot address capable
CARRIER SPECIFICATION
See also System Specification
ELECTRICAL CONNECTIONS
Railbus carrier connector
8020-CE-RH …………………………………………………………female in
8021-CE-LH…………………………………………………………..male out
Extender cable connector ……………………Sub-D, 37-pin female
System Power cable connections* …………..screw terminal (x6)
System Power cable conductor size………………2.5mm2 (max.)
* The six terminals for the System Power connections must be made
in addition to connecting the Extender cable. The Terminals on the
left- and right- hand extenders indicate which connections need to be
made for System Power (HVCC + and HVCC -) and an internal
ground connection (SGND).
MECHANICAL
Dimensions (overall) ……………………42 (w) x 168 (d) x 37 (h)mm
Weight. ……………………………………………………………………135g
Mounting method …………………………….integral DIN-rail fixings
DIN rail types
………………….‘Top hat’, 35 x 7.5mm or 35 x 15mm to EN 50022
……………………………………………………….G-section, to EN 50035
PART NUMBERS
Carrier Extender, Right-hand 8020-CE-RH
Carrier Extender, Left-hand 8021-CE-LH

8-channel Field Terminals
SafetyNet IO Modules use standard MOST
8-channel Field Terminals. Depending on
the application, the Field Terminals may be
for general purpose, non-arcing or nonincendive field wiring, may incorporate
fused disconnects and may be for 2-, 3- or
4-wire transmitters.
Fused disconnect
The fused disconnect Field Terminals
incorporate a 2A fuse that can be partially
withdrawn from the Field Terminal to act as
a loop disconnect.
Tag strip
Each Field Terminal is supplied with an
integral tag strip, which is hinged to provide
access to the wiring terminals and the fuse
disconnects.
Field Terminal clicks
on to Carrier
The Field Terminal is easily removed from
the Carrier – it is held in place by a sprung
latch that can be released without the need
for tools. This simplifies connection of the
field wiring. The Field Terminal is secured in
place by the insertion of the IO Module.
Wiring to Field Terminals
SafetyNet IO Modules all use 8-channel
Field Terminals, to which wiring with a cross
section of up to 2.5mm2 can be connected.
Each termination point is clearly numbered
to simplify recognition of each terminal. The
two rows of terminals are offset to allow
access to the lower row when wiring is in
place.

Electric tricycle truck, agricultural tricycle, elderly vehicle, warehouse truck

Electric tricycle truck, agricultural tricycle, elderly vehicle, warehouse truck

 

 


Powerful performance: With a top speed of over 20 miles per hour and a standard range of 50 miles
per charge. The standard 18 tube controller,
upgraded powerful silent 1000W brushless differential motor, and dedicated 60V 45Ah lead-acid battery power supply reduce the weight of the
vehicle, making the driving range and load capacity stronger.

Practical: Newly designed integrated perforated cargo box, concave steel box, vehicle size: 114 * 39 * 63.5 inches, cargo box
size: 70.8 * 39 * 16 inches, vehicle weight: 353 pounds, rated load: 1100 pounds, front/rear brake type: front/rear brake:
drum brake, parking brake: manual brake, charging time: 6-8 hours- 8 hours

Our electric tricycle is equipped with sturdy tires that provide excellent grip on any terrain. The front wheels are lengthened
with hydraulic shock absorbers to reduce collisions and provide smooth driving. The front bumper is thickened, and the body
bumper is made of sturdy metal to ensure strength and service life, providing a solid foundation for your ride.

Excellent features: Luxurious LCD instrument panel, safe and reliable front LED headlights – providing excellent visibility
through directional signals, brake lights, and powerful headlights. Dual rearview mirrors ensure visibility.
The electric tricycle is also equipped with an anti-skid controller. When reversing downhill, the controller will maintain a constant slow reversal and rolling speed to ensure your personal safety.

[Easy to use] Adult electric tricycles can be used as electric tricycles for daily and short distance travel.
Electric motorcycles can be leisurely ridden on the streets or easily cross hills. You can also use it to load goods,
which can help you transport goods and provide higher efficiency for agriculture and transportation.

Safe and reliable configuration: The electric tricycle has a climbing gear, which is sturdy and strong when climbing

at low speeds, greatly increasing the load capacity to meet the needs of climbing and pulling heavy objects.
The three speeds can be easily adjusted through the variable speed control knob, and the display screen will
show the remaining power, range, and current speed, allowing you to quickly check the battery status and add color and happiness to your life.

Friendly reminder of logistics time: The arrival time of electric tricycles is about 45-60 days. If you don’t want
to wait, please forgive us. 1. Because our electric tricycle factory has undergone performance and safety testing;
The packaging must be sturdy to avoid damage during transportation. 3. Electric tricycles are transported by sea,
so the transportation time is slightly longer. If you have any questions, please feel free to contact us and we will provide you with the best quality service and after-sales protection.



Search for products

Back to Top
Product has been added to your cart